Hi There, I have a workmaster computer and Logicmaster LM1 software and cant talk to a CPU101 but can talk to a 104,105,106 cpu. What way do you communicate with a CPU101 other that the small programer.

-- Jim (eleator555@hotmail.com), August 04, 2004

Answers

You may be able to communicate to the CPU using DirectSoft (www.automationdirect.com), and a RS 232 communications module such as a D3-232DCU. Koyo made the GE Series One. They now provide them in the form of a DL-305 from Automation Direct (a subsiderary of Koyo). You need to provide the entire GE part number of the CPU to cross- reference the CPU to current AD models, and get the right DCU. Also you may want to post this question on www.plctalk.net.

-- Mike Lardner (mlardner@lardnerelevator.com), August 09, 2004.

There was a specific version of GE LogicMaster software for the CPU101. If you need to have a program converted to a newer CPU version, we may be able to help you out.

-- Chris Maida (chris.maida@vacontrols.com), August 10, 2004.